This part specifies the system composition, main technical parameters, functions, protection, process and test requirements of the static var compensation device (SVC) closed water cooling device. This section applies to the subsystem of SVC used in power transmission systems and distribution systems - closed water cooling devices (hereinafter referred to as water cooling devices). SVC can be applied to power systems of 6kV and above, and the thyristor-controlled branches can be directly connected to 6kV ~ 66 (63) kV systems.
DL/T 1010.5-2006 Referenced Document
DL/T 801-2002 Requirements of water quality and internal cooling water system for large generator
GB 50235-1997 Code for construction and acceptance of industrial metallic piping
GB/T 14598.10-1996 Electrical relays. Part 22: Electrical disturtance tests for measuring relays and protection equipment. Section 4: Fast transient disturbance test
GB/T 14598.13-1998 Electrical disturbance tests for measuring relays and protection equipment. Part 1: 1MHz burst disturbance tests
GB/T 14598.14-1998 Electrical disturbance tests for measuring relays and protection equipment. Part 2: Electrostatic discharge tests