1.1 This specification covers nonreinforced concrete pipe with rubber gasket joints to be used for the conveyance of irrigation water with working pressures, including hydraulic transients, as shown in Table 1.
1.2 A complete metric companion to Specification C505 has been developed Note 18212;This specification is for manufacturing and purchase only and does not include requirements for bedding, backfill, installation, or field repairs. The owner is cautioned that he must correlate field conditions with the characteristics of the pipe specified and provide inspection during installation.
Internal Designated Diameter, in. | Wall Thickness,A in. | Working Pressure,B ft | Required Hydrostatic Test Pressure,C psi | Minimum Three-Edge- Bearing Load, lbf/linear ft |
---|---|---|---|---|
6 | ¾ | 30 | 40 | 1300 |
8 | 1 | 30 | 40 | 1350 |
10 | 1¼ | 30 | 40 | 1400 |
12 | 1½ | 30 | 40 | 1500 |
15 | 17/8 | 30 | 40 | 1650 |
18 | 2¼ | 30 | 40 | 1800 |
21 | 25/8 | 30 | 40 | 1900 |
24 | 3 | 30 | 40 | 2000 |
A Thinner walls are not prohibited on pipe units not over 4 ft in length, but the thickness of such walls shall not be less than the internal diameter divided by 10.
B With the exception of 21 and 24-in. pipe, higher working pressures are not prohibited to be used up to a maximum of 50 ft for 6 through 12-in. diameters, and 40 ft for 15 through 18-in. diameters. I......