This part of IEC 60255 is based on IEC 61000-4-3, referring to that publication where
applicable, and specifies the general requirements for radiated electromagnetic field immunity
tests for measuring relays and protection equipment for power system protection, including the
control, monitoring and process interface equipment used with those systems.
The objective of the tests is to confirm that the equipment under test (EUT) will operate
correctly when energised and subjected to an electromagnetic field from a radiation source
operating within the frequency range 80 MHz to 2,7 GHz.
NOTE 1 The product standard IEC 60255-22-6 (based on IEC 61000-4-6) establishes the immunity of measuring
relays and protection equipment over the frequency range of 0,15 MHz to 80 MHz.
NOTE 2 The test methods defined in this standard are structured for the primary objective of establishing
adequate repeatability of results at various test facilities for qualitative analysis of effects. The test methods using a portable transmitter1 are not taken into consideration here because the EMC directive now specifies a sweep test,
calibrated field strengths must be used and the portable transmitter test is not generally reproducible.
The requirements specified in this standard are applicable to measuring relays and protection
equipment in a new condition, and all tests specified are type tests only.
BS EN 60255-22-3:2008 history
2014BS EN 60255-26:2013 Measuring relays and protection equipment. Electromagnetic compatibility requirements
2008BS EN 60255-22-3:2008 Measuring relays and protection equipment - Part 22-3:Electrical disturbance tests - Radiated electromagnetic field immunity
2001BS EN 60255-22-3:2001 Electrical relays - Electrical disturbance tests for measuring relays and protection equipment - Radiated electromagnetic field disturbance tests