?1.1 Scope.
1.1.1 This code shall apply to the storage, handling, and use of flammable and combustible liquids, including waste liquids, as herein defined and classified.
1.1.2 This code shall not apply to the following:
(1) Any liquid that has a melting point equal to or greater than 37.8°C (100°F) or that does not meet the criteria for fluidity given in the definition for liquid in Section 1.7
(2) Any liquefied gas or cryogenic liquid as defined in Chapter 3
(3) Any liquid that does not have a flash point, but which is capable of burning under certain conditions; such liquids include certain halogenated hydrocarbons and certain mixtures of flammable or combustible liquids and halogenated hydrocarbons
(4) Any aerosol product
(5) Any mist, spray, or foam
1.1.3 This code shall also not apply to the following:
(1) Transportation of flammable and combustible liquids as governed by the U.S. Department of Transportation
(2) Storage, handling, and use of fuel oil tanks and containers connected with oil-burning equipment
NFPA 30-2003 history
2021NFPA 30-2021 Flammable and Combustible Liquids Code (Effective Date: 8/31/2020)
2015NFPA 30-2015 Flammable and Combustible Liquids Code (Effective Date: 5/19/2014; ALERT: THIS STANDARD HAS BEEN MODIFIED BY A TIA OR ERRATA)
2012NFPA 30-2012 Flammable and Combustible Liquids Code Effective Date: 6/20/2011
2007NFPA 30-2007 Flammable and Combustible Liquids Code 2008 Edition
2003NFPA 30-2003 Flammable and Combustible Liquids Code
1997NFPA 30-1996 Flammable and Combustible Liquids Code Handbook