IEC 61008-1:2006 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
This International Standard applies to residual current operated circuit-breakers functionally
independent of, or functionally dependent on, line voltage, for household and similar uses, not
incorporating overcurrent protection (hereafter referred to as RCCBs), for rated voltages not
exceeding 440 V a.c. and rated currents not exceeding 125 A, intended principally for
protection against shock-hazard.
These devices are intended to protect persons against indirect contact, the exposed conductive
parts of the installation being connected to an appropriate earth electrode. They may be used
to provide protection against fire hazards due to a persistent earth fault current, without the
operation of the overcurrent protective device.
RCCBs having a rated residual operating current not exceeding 30 mA are also used as a
means for additional protection in case of failure of the protective means against electric
shock.
This standard applies to devices performing simultaneously the functions of detection of the residual current, of comparison of the value of this current with the residual operating value and of opening of the protected circuit when the residual current exceeds this value.
NOTE 1 The requirements for RCCBs are in line with the general requirements of IEC 60755. RCCBs are essentially intended to be operated by uninstructed persons and designed not to require maintenance. They may be submitted for certification purposes.
NOTE 2 Installation and application rules of RCCBs are given in IEC 60364.
They are intended for use in an environment with pollution degree 2.
They are suitable for isolation.
Special precautions (e.g. lightning arresters) may be necessary when excessive overvoltages are likely to occur on the supply side (for example in the case of supply through overhead lines) (see IEC 60364-4-443).
RCCBs of the general type are resistant to unwanted tripping including the case where surge voltages (as a result of switching transients or induced by lightning) cause loading currents in the installation without occurrence of flashover.
RCCBs of the S type are considered to be sufficient proof against unwanted tripping even if the surge voltage causes a flashover and a follow-on current occurs.
NOTE 3 Surge arresters installed downstream of the general type of RCCBs and connected in common mode may cause unwanted tripping.
NOTE 4 For RCCBs having a degree of protection higher than IP20 special constructions may be required.
Particular requirements are necessary for
– Residual current operated circuit-breakers with integral overcurrent protection (see IEC 61009);
– RCCBs incorporated in or intended only for association with plugs and socket-outlets or
with appliance couplers for household or similar general purposes.
NOTE 5 For the time being, for RCCBs incorporated in, or intended only for socket-outlets or plugs, the requirements of this standard in conjunction with the requirements of IEC 60884-1 may be used as far as applicable.
The requirements of this standard apply for normal environmental conditions (see 7.1).
Additional requirements may be necessary for RCCBs used in locations having severe
environmental conditions.
RCCBs including batteries are not covered by this standard.
IEC 61008-1:2006 history
2016IEC 61008-1:2010/AMD1:2012/COR1:2016 Corrigendum 1 - Amendment 1 - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBS) - Part 1: General rules
2014IEC 61008-1:2010/AMD2:2013/COR1:2014 Corrigendum 1 - Amendment 2 - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
2013IEC 61008-1:2010/AMD2:2013 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
2013IEC 61008-1:2013 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
2012IEC 61008-1:2010/AMD1:2012 Amendment 1 - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
2012IEC 61008-1:2012 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
2010IEC 61008-1:2010 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
1970IEC 61008-1:1996/AMD2:2006 Amendment 2 - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
2006IEC 61008-1:2006 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
1970IEC 61008-1:1996/AMD1:2002 Amendment 1 - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
2002IEC 61008-1:2002 Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) - Part 1: General rules
1996IEC 61008-1:1996 Residual Current Operated Circuit-Breakers without Integral Overcurrent Protection for Household and Similar Uses (RCCBs) - Part 1: General Rules (Edition 2.0)
1970IEC 61008-1:1990/AMD2:1995 Amendment 2 - Electrical accessories - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCB's). Part 1: General rules.
1970IEC 61008-1:1990/AMD1:1992 Amendment 1 - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCB's). Part 1: General rules.
1970IEC 61008-1:1990/COR1:1990 Corrigendum 1 - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCB's). Part 1: General rules
1990IEC 61008-1:1990 Amendment 2 Electrical accessories - Residual current operated circuit-breakers without integral overcurrent protection for household and similar uses (RCCBs) – Part 1: General rules (Edition 1.0)