ULC-S644-2000
- Replace By
-
CAN/ULC-S644:2016
- Replace
-
CAN/ULC-S644-M90
- Scope
- Scope 1.1
These requirements cover emergency breakaway fittings intended only for
flammable and combustible liquid service including gasoline with up to 15%
ethanol. 1.2
An emergency breakaway fitting is intended for use with dispensing devices to
allow separation of the hose nozzle valve and/or hose from the dispenser and
prevent loss of liquid in the event that the vehicle drives away before the
hose nozzle valve is removed from the vehicle's tank filler neck. 1.3
An emergency breakaway fitting is intended to be installed between the hose
nozzle valve and the dispenser. 1.4
Requirements for the installation and use of equipment handling flammable and
combustible liquids may be included in the National Fire Code of Canada and the
regulations of the authority having jurisdiction.
ULC-S644-2000 history
- 2000 ULC-S644-2000 Standard for Emergency Breakaway Fittings for Flammable and CombustibleLiquids
ULC-S644-2000 Standard for Emergency Breakaway Fittings for Flammable and CombustibleLiquids has been changed from CAN/ULC-S644-M90-1990 Standard for Emergency Breakaway Fittings for Flammable and Combustible Liquids.
ULC-S644-2000 Standard for Emergency Breakaway Fittings for Flammable and CombustibleLiquids was changed to CAN/ULC-S644:2016 STANDARD FOR EMERGENCY BREAKAWAY FITTINGS FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS.