For the first time, this standard takes business demand orientation as the core principle of data center design. Compared with the traditional YD/T 2441 standard which focuses on infrastructure, it presents three major innovations in architecture:
| Comparison dimension | Traditional standard | This business-oriented standard |
|---|---|---|
| Design starting point | Infrastructure compliance | Business scenario matching |
| Energy efficiency index | Single PUE requirement | PUE+WUE+CUE three-dimensional system |
| Technical path | General Solution | Modularization + Liquid Cooling Customization |
For the first time, the requirement of 300-meter tap water supply radius is clarified, and the minimum distance from the source of danger is stipulated:
Detailed three types of liquid cooling technical specifications:
Immersed liquid cooling must comply with the sealing requirements of YD/T 3979, and the boiling point of the coolant should be higher than 150℃; class=instrument>Cold plate liquid cooling According to the requirements of YD/T 3980, the leakage detection response time is ≤30 seconds; the spray system needs to be equipped with a double filtration device.
Establish a four-level energy efficiency evaluation model:
| Indicators | First year requirements | Next year requirements | Measurement method |
|---|---|---|---|
| PUE | ≤1.4 | ≤1.3 | Total IT equipment power consumption/total energy consumption |
| WUE | ≤1.6L/kWh | ≤1.4L/kWh | Water consumption/IT power consumption |
| Rack utilization | ≥70% | ≥90% | Actual shelf power/design power |
Requires the establishment of a three-dimensional monitoring system: