YD/T XXXX-2023 standard defines for the first time the three major operating modes of the adaptive dual-cold source computer room temperature control system:
| Operation mode | Trigger condition | Energy efficiency ratio requirement | Typical energy saving rate |
|---|---|---|---|
| Compressor cooling mode | Inlet water temperature ≥30℃ | ≥2.75(Level 3) | Benchmark value |
| Mixed operation mode | 8℃≤Inlet water temperature <30℃ | Natural cooling 10+compressor 2.95 | 35-60% |
| Natural cooling mode | Inlet water temperature <8℃ | ≥10(Level 3) | Above 80% |
The system needs to verify its cooling capacity under two standard operating conditions:
The actual application case of a data center shows that through class=instrument>Three-way valve dynamically adjusts water flow, and the energy saving effect in mixed mode is improved by 12%. The system needs to have:
It is recommended to give priority to energy efficiency ratio level 1 products (natural cooling mode ≥14, compressor mode ≥3.15), and the investment recovery period is about 2-3 years.