| Technical dimensions | DC system requirements | AC system comparison |
|---|---|---|
| Voltage level | -48V/240V/336V | 380V/400V |
| Current specification | 200A-1250A | 400A-2500A |
| Voltage drop limit | ≤0.5V(-48V) | ≤1% rated value |
Copper content of copper busbar ≥99.9%, conductivity ≥97% IACS. Single section length ≤3m, aluminum alloy shell thickness ≥2.0mm, cold rolled steel plate ≥1.5mm. plug-in box must be equipped with anti-loosening device, and the temperature rise at the plug-in point ≤60K.
Non-20℃ environment needs to be corrected according to the formula: ΔVt=ΔV20×[1+0.00393(t-20)], where the copper conductor temperature coefficient α=0.00393.
MTBF≥100,000 hours, must pass the accelerated life test specified in the YD/T 282-2000 standard, including:
-40℃~70℃ temperature cycle
10Hz-55Hz mechanical vibration
93%RH constant humidity