Core changes in the standard revision
Technical dimensions | Requirements of the 2017 version | New/revised content of the 2023 version |
Voltage level | Upper limit not specified | The upper limit of the AC port voltage is determined to be 35kV |
Functional requirements | Basic power control | 8 new functions such as primary frequency modulation and inertia response |
Safety protection | Basic insulation requirements | 3 new requirements such as equipotential connection and capacitor residual energy protection |
Analysis of key technical indicators
Core parameters of electrical performance
Energy storage converters must meet the following requirements under rated operating conditions:
- Four-quadrant power dynamic adjustment range: active/reactive output is continuously adjustable within ±110% rated value
- Conversion efficiency: Class A1 equipment charging and discharging efficiency ≥96% (including auxiliary power loss)
- Fault ride-through capability: 0V voltage lasts for 150ms without disconnection from the grid
Comparison of typical application scenarios
Classification basis | Class A1 (high voltage grid connection) | Class B2 (low voltage power distribution) |
Voltage level | >1000V | 380V |
Dynamic reactive response | ≤30ms | Optional |
Protection level | IP54 (outdoor) | IP20 (indoor) |
Standard implementation recommendations
Product development focus
- Topology selection: Cascade topology is suitable for high voltage scenarios of 10kV and above
- Fault ride-through algorithm optimization: Need to support 3 consecutive low-high voltage ride-throughs
- Safety protection design: capacitor discharge time ≤ 5s (60V/20J)
Key points for testing and certification
- Electromagnetic compatibility testing needs to distinguish between A1/B2 equipment limits
- Type inspection includes 72-hour salt spray test (outdoor type)
- Factory inspection requires 100% power frequency withstand voltage test
Technology evolution analysis
This standard introduces the inertia response requirement for the first time (formula: ΔP=-Tj/fn×df/dt×Pn), promoting the upgrade of energy storage systems from simple power regulation to grid support functions, where:
- Inertia time constant Tj is set to 4-14 seconds
- Response time ≤ 100ms, adjustment time ≤ 300ms