| Key elements | Requirements in the environmental impact assessment stage | Requirements in the acceptance stage |
|---|---|---|
| Wastewater treatment facilities | Designed treatment capacity, process route | Actual operating load ≥ 75%, disinfection effect monitoring |
| Temporary storage of medical waste | Anti-seepage design of temporary storage site | Verification of disposal agreement, inspection of transfer joint form |
| Environmentally sensitive targets | Impact prediction and analysis | Comparison of actual monitoring data |
Mercury-containing wastewater from the dental department must be collected and treated separately, and the operation records of the special treatment facilities should be checked during acceptance. A case study of a tertiary hospital showed that the mercury removal rate reached 98.7% after the sulfide precipitation process.
Double disinfection" system must be implemented for wastewater from infectious wards, and special attention should be paid to pathogen indicators such as Mycobacterium tuberculosis during monitoring.
| Problem type | Typical case | Rectification suggestions |
|---|---|---|
| Sewage discharge exceeds the standard | COD of a hospital exceeds the standard by 1.8 times | Add hydrolysis acidification pretreatment unit |
| Medical waste management defects | Transfer records missing | Establish an electronic ledger system |