ASTM C1609/C1609M-24 is the core standard for evaluating the flexural properties of fiber-reinforced concrete (FRC). It utilizes the third-point loaded beam test method under a The new standard specifies that: Specimens must be cast in a single layer (7.2.1), the use of vibrators is prohibited (7.2.2), and only external vibration molding is permitted. Typical specimen dimensions are: A closed-loop servo-controlled testing machine (6.1) must be used, and the deflection measurement device must eliminate the influence of support system deformation (Figure 1/2). Data acquisition frequency requirements:
Test principle and parameter system
Parameter Definition Calculation formula Engineering significance First peak strength (f₁) The first extreme point of the load-deflection curve f₁=P₁L/bd² Represents the bearing capacity before cracking Residual strength (f₁₅₀ᴰ) Residual load at deflection L/150 f₁₅₀ᴰ=P₁₅₀ᴰL/bd² Evaluation of post-cracking ductility Equivalent bending strength (fₑ,₁₅₀ᴰ) Energy absorption conversion strength fₑ,₁₅₀ᴰ=150T₁₅₀ᴰ/bd² Comprehensive performance indicators
Key implementation requirements
Specimen Preparation Specifications
Test System Configuration
Technical points analysis
Size effect warning: The standard specifically points out (Note 5) that the specimen size will significantly affect the test results, especially when the ratio of fiber length to specimen cross-sectional size is greater than 1/3, the fiber orientation effect will make the data incomparable.
Precision Verification: Single laboratory coefficient of variation (Table 2/3):